3-D Animation of Test Specimen
Sprinkler Piping Subsystems Test Specimen on NCS |
 |
UB-Nonstructural Component Simulator
Two-level shake table capable of reproducing in real-time the full-scale floor motions expected at two consecutive building levels |
 |
Partitions Subsystem In-Plane Experiments
Specimens 1, 2 & 3 (Basic), & Specimen 4 (Gypsum connected to top track)
Top slip track acted as intended:
- Limited damage observed in in-plane wall
- Damage concentrated in return walls top tracks
- Spec 4 performed similarly to specs 1 to 3 after failure of connection of gypsum to top track
- Crushing of gypsum in wall corners
|
 |
Partitions Subsystem In-Plane Experiments
Specimens 11, 12 & 13 (Bookshelves attached)
Damage concentrated along cornerbeads
No damage observed around attachments of bookshelves to partition walls
Books in bookshelf fell down
|
 |
Partitions Subsystem In-Plane Experiments
Specimens 14, 15 & 16 (Simulated rigid ceiling)
Equivalent rigid ceiling weight attached to the walls
Damage similar to specimens w/bookshelves attached
|
 |
Partitions Subsystem Out-of-Plane Experiments
Specimens 40, 41 & 43, and 39, 45 & 47
(Bookshelf/Walls without and with Returns)
Screws pulled out from gypsum to stud connections & damage in bookshelf connectors
Damage along horizontal joints between gypsum wallboards and along cornerbeads
Collapse of Specimens 40, 43b & 47 (All of them, re-used walls) |
 |
Partitions Subsystem Out-of-Plane Experiments
Specimens 42, 44 & 46 (eq. ceiling/Walls w/ returns)
Gypsum boards crushed around fence staples connection
Screws pulled out from gypsum to stud connections
Damage at top and bottom ends of cornerbeads
Equivalent ceiling completely detached from wall
(Specimen 46) |
 |
Partition Wall Subsystems Out-of-Plane Experiments
Specimens 48, 49 & 50 (Partial Height Braced Walls with Returns)
Screws pulled from connection of braces to top track
Buckling of steel braces
Buckling of top track around brace connections |
 |
Partition Wall Subsystems Out-of-Plane Experiments
Specimens 48, 49 & 50 (Partial Height Braced Walls with Returns)
Screws pulled from connection of braces to top track
Buckling of steel braces
Buckling of top track around brace connections |
|
|
Seismic testing at the University at Buffalo of suspended ceiling system showing initiation of collapse from the side of the ceiling.
Total runtime: 1:08
|
|
|
Seismic testing at the University at Buffalo of suspended ceiling system showing initiation of collapse from the center of the ceiling.
Total runtime: 0:28
|
|
|
Seismic testing at the University at Buffalo of suspended ceiling system showing initiation of collapse from the perimeter of the ceiling.
Total runtime: 1:00 |
|
|
Seismic testing at the University at Buffalo of suspended ceiling system showing progressive collapse of the ceiling system.
Total runtime: 0:43
|
|
|
Out-of-plane seismic testing at the University at Buffalo of cold-formed steel framed gypsum partition walls with bookshelf attached.
Total runtime: 0:57 |
|
|
Seismic testing at the University at Buffalo of full-scale black iron threaded sprinkler piping subsystem.
Total runtime: 0:57
|
|
|
Cyclic testing at the University at Buffalo of sprinkler piping tee-joints showing first leakage of the joint.
Total runtime: 0:40
|
|
|
Seismic testing at the University at Buffalo of full-scale thermoplastic (CPVC) threaded sprinkler piping subsystem showing failure of a branch line tee-joint.
Total runtime: 5:39
|